The REFCO Gobi II is a high-performance condensate removal pump designed for use with air conditioning systems ranging from 6,000 Btu/H (1.75kW) up to 120,000 Btu/H (35 kW). It features a digital water sensor, universal voltage compatibility, and user-configurable flow settings, making it suitable for various HVAC applications.

Important Note: REMOVE ALL OLD WIRING. New power and alarm wires are included with this pump. These new wires MUST be used and properly grounded during installation. Pump wiring has been updated from all previous versions.

REFCO Gobi II Condensate Pump and Accessories

Image 1: REFCO Gobi II Condensate Pump with included power cables and discharge tubing.

2. การตั้งค่าและการติดตั้ง

Proper installation is crucial for the safe and efficient operation of the Gobi II pump. Refer to the detailed wiring diagram and follow all local electrical codes.

2.1 คำแนะนำในการเดินสายไฟ

The Gobi II pump utilizes a new wiring configuration. It is imperative to replace any existing wiring with the new power and alarm wires provided. Ensure all connections are secure and correctly grounded.

Wiring diagram for REFCO Gobi II Condensate Pump showing new power and alarm wire connections

Image 2: Wiring diagram illustrating the new power and alarm wire connections for the Gobi II pump. Old wiring must be removed and replaced with the new, grounded wires.

2.2 การจัดวาง

The pump is designed for under A/C unit mounting. Consider the maximum suction height of 10 ft (3 m) and maximum head of 65.6 ft (20 m) when determining the pump's location relative to the condensate source and discharge point.

2.3 Discharge Line Connection

Connect the provided 1/4" I.D. (6.25 mm) discharge tube to the pump's outlet. Ensure the tube is routed without kinks or sharp bends to allow for unobstructed condensate flow.

3. คู่มือการใช้งาน

The Gobi II pump operates automatically based on its digital water sensor. Once properly installed and powered, it will activate to remove condensate when the water level in the reservoir reaches a predetermined point.

  • การทำงานอัตโนมัติ: The pump's digital sensor detects condensate levels and initiates pumping cycles as needed.
  • User-Configurable Flow: The pump features user-configurable flow settings to optimize performance for various AC unit capacities. Refer to the specific configuration guide for detailed instructions on adjusting flow settings.
  • การทำงานที่เงียบ: The pump is designed for quiet operation, typically producing 20dBA at 3 ft (1 m) distance.

4. การบำรุงรักษา

Regular maintenance ensures the longevity and optimal performance of your Gobi II condensate pump.

  • การทำความสะอาดเซ็นเซอร์: Periodically inspect and gently clean the digital water sensor to prevent buildup that could affect its accuracy. Disconnect power before cleaning.
  • Reservoir Inspection: Check the pump's reservoir for any debris or sludge accumulation. Clean as necessary to maintain clear operation.
  • ตรวจสอบท่อระบายน้ำ: Ensure the discharge line remains clear of obstructions and kinks. Verify that water is flowing freely from the discharge point.

5 การแก้ไขปัญหา

If you encounter issues with your Gobi II pump, refer to the following troubleshooting guide:

ปัญหาสาเหตุที่เป็นไปได้สารละลาย
ปั๊มไม่ทำงานNo power; Sensor malfunction; Motor failureCheck power supply and connections; Clean sensor; Contact qualified technician if motor is suspected to be faulty.
Pump running continuously or too frequentlySensor dirty or faulty; Air in suction line; Leak in systemClean sensor; Check for air leaks in suction line; Inspect AC unit for excessive condensate production or leaks.
Water overflow from AC unit or pumpDischarge line blocked or kinked; Pump failure; Sensor not activating pumpClear discharge line; Check pump operation; Clean or replace sensor.
Excessive noise or gurglingAir in pump or lines; Improper installation; Debris in pumpBleed air from system; Ensure proper mounting and level installation; Inspect for and remove debris.

6. ข้อมูลจำเพาะ

  • แบบอย่าง: Gobi II
  • อัตราการไหลสูงสุด: 11 GPH (42 l/h)
  • แรงดูดสูงสุด: 10 ft (3 m) self-priming
  • หัวหน้าสูงสุด: 65.6 ฟุต (20 ม.)
  • ระดับเสียง: 20dBA at 3 ft (1 m) / 19dBA at 1 EN ISO 3744:2010
  • เล่มที่tage: 100 ~ 240 VAC 50/60 Hz (auto sensing universal power input)
  • การใช้พลังงาน: 8 watts (during maximum operation at 110V)
  • รีเลย์สัญญาณเตือน: 10 Amps NO/NC contacts with integrated replaceable HRC 10A fuse 5 × 20 mm
  • น้ำหนัก: 1.3 Lbs. (600g)
  • Discharge Tube: 1/4" I.D. (6.25 mm) × 3.3 ft (1 m)
  • การป้องกัน: Class II double insulation, Fully potted, IP-44
  • อุณหภูมิการทำงาน: Ambient 37.5°F to 104°F (3°C to 40°C) / Water 41°F to 77°F (5°C to 25°C)
  • การปฏิบัติตาม: Conforms to UL:778 and certified to CSA C22.2#68
  • ขนาดสินค้า : ยาว 11.3 นิ้ว x กว้าง 2.09 นิ้ว x สูง 2.09 นิ้ว
  • วัสดุ: พลาสติก

7. การรับประกันและการสนับสนุน

For warranty information and technical support, please refer to the documentation provided with your purchase or contact REFCO directly through their official webซื้อได้จากเว็บไซต์หรือตัวแทนจำหน่ายที่ได้รับอนุญาต เก็บหลักฐานการซื้อไว้เพื่อใช้ในการเคลมประกัน

เอกสารที่เกี่ยวข้อง - Gobi II

พรีview คู่มือการติดตั้งและการใช้งานปั๊มคอนเดนเสท Gobi II
คู่มือครอบคลุมสำหรับปั๊มคอนเดนเสท REFCO Gobi II ครอบคลุมถึงการติดตั้ง การใช้งาน การบำรุงรักษา และการแก้ไขปัญหาสำหรับระบบ HVAC/R
พรีview คู่มือการติดตั้งและการใช้งานปั๊มคอนเดนเสท REFCO Gobi II
คู่มือฉบับสมบูรณ์เกี่ยวกับปั๊มคอนเดนเสท REFCO Gobi II ครอบคลุมรายละเอียดการติดตั้ง การใช้งาน ข้อควรระวังด้านความปลอดภัย ข้อมูลจำเพาะทางเทคนิค และการแก้ไขปัญหา มาพร้อมฟีเจอร์ต่างๆ เช่น โหมดเงียบที่กำหนดค่าได้ ไฟ LED แสดงสถานะการวินิจฉัย การเชื่อมต่อ USB และขอบเขตการใช้งานที่กว้างขวาง
พรีview ปั๊มคอนเดนเสท REFCO GOBI II: คู่มือการติดตั้งฉบับย่อ
คู่มือฉบับย่ออย่างเป็นทางการสำหรับปั๊มคอนเดนเสท REFCO GOBI II (รุ่น 3004145) ให้ข้อมูลสำคัญเกี่ยวกับการติดตั้ง การใช้งาน ความปลอดภัย และการบำรุงรักษาเพื่อการกำจัดคอนเดนเสทอย่างมีประสิทธิภาพในระบบ HVAC
พรีview คู่มือการติดตั้งและทางเทคนิคของปั๊มคอนเดนเสทอเนกประสงค์ REFCO Combi 3004146
เอกสารนี้ให้ข้อมูลการติดตั้ง ข้อมูลจำเพาะทางเทคนิค แนวทางด้านความปลอดภัย และข้อมูลการแก้ไขปัญหาอย่างครอบคลุมสำหรับปั๊มคอนเดนเสทสากล Combi REFCO (รุ่น 3004146)
พรีview เรฟโค วีAMP-F คู่มือการใช้งานปั๊มคอนเดนเสท
เอกสารนี้ให้คำแนะนำที่ครอบคลุมสำหรับการติดตั้ง การใช้งาน การบำรุงรักษา และการแก้ไขปัญหาของ Refco VAMPปั๊มคอนเดนเสท -F ประกอบด้วยแนวทางด้านความปลอดภัย ข้อมูลจำเพาะ และข้อมูลชิ้นส่วน
พรีview รีฟโก้ วีAMPคู่มือการใช้งานปั๊มคอนเดนเสท -X
คู่มือการใช้งานนี้ให้ข้อมูลโดยละเอียดเกี่ยวกับ REFCO VAMPปั๊มคอนเดนเสท -X ครอบคลุมรายละเอียดเฉพาะ การติดตั้ง การใช้งาน การบำรุงรักษา แนวทางความปลอดภัย และการแก้ไขปัญหา มีให้บริการในภาษาอังกฤษ เยอรมัน ฝรั่งเศส อิตาลี และสเปน