Altronix AL1012ULACMCB

Altronix AL1012ULACMCB Power Supply/Charger User Manual

Model: AL1012ULACMCB

1. บทนำ

The Altronix AL1012ULACMCB is a robust power supply/charger designed to convert 115VAC 60Hz input into eight (8) independently controlled 12VDC non-power limited, fuse-protected outputs. It provides a total of 10 amp continuous supply current. This unit supports both Fail-Safe and Fail-Secure configurations for its outputs. A key feature is the fire alarm disconnect, which allows for emergency egress by individually selecting this function for any or all of the eight outputs. The AL1012ULACMCB is a PTC protected version, ensuring enhanced safety and reliability.

2. ข้อมูลด้านความปลอดภัย

Please read and understand all instructions before installing or operating this unit. Failure to do so may result in injury or damage to the unit.

  • ความเสี่ยงจากไฟฟ้าช็อต: Disconnect all power sources before servicing. Only qualified personnel should perform installation and maintenance.
  • การระบายอากาศ : ตรวจสอบให้แน่ใจว่ามีการระบายอากาศเพียงพอรอบๆ เครื่องเพื่อป้องกันความร้อนสูงเกินไป
  • ความปลอดภัยของแบตเตอรี่:
    • Avoid short circuits when handling batteries.
    • Do not charge batteries in a sealed container.
    • Keep sparks and flame away from batteries.
    • Use only recommended battery types (Sealed Lead-Acid, 12V, 12AH).
  • การเปลี่ยนฟิวส์: Replace fuses only with the same type and rating as marked on the unit.
  • สำหรับใช้ภายในอาคารเท่านั้น: This unit is designed for indoor use in a controlled environment.

3. สินค้าหมดview

The AL1012ULACMCB unit is housed within a durable metal enclosure, designed for secure installation. It comprises a main power supply board and a separate distribution board for the eight independent outputs. A sealed lead-acid battery is typically housed within the enclosure for backup power.

Altronix AL1012ULACMCB Power Supply/Charger with open enclosure showing internal components and battery.
รูปที่ 3.1: ภายใน view of the Altronix AL1012ULACMCB Power Supply/Charger. The image displays the main power supply board at the top, the eight-output distribution board below it, and a 12V, 12AH sealed lead-acid battery at the bottom right. Wiring connections, including a green ground wire, are visible. An instruction diagram is affixed to the inside of the enclosure door.

ส่วนประกอบหลัก:

  • Main Power Supply Board: Converts AC input to regulated DC power and manages battery charging.
  • Eight-Output Distribution Board: Provides eight individually fuse-protected 12VDC outputs. Each output can be configured for Fail-Safe or Fail-Secure operation.
  • Fire Alarm Disconnect Terminals: Allows integration with a fire alarm system to disconnect power to specified outputs during an alarm event.
  • ขั้วแบตเตอรี่: For connecting a 12V sealed lead-acid backup battery.
  • AC Input Terminals: For connecting 115VAC 60Hz power.

4. การตั้งค่าและการติดตั้ง

Installation should be performed by qualified service personnel in accordance with all local and national electrical codes.

4.1 การติดตั้งสิ่งที่แนบมา

  1. Select a suitable, dry, and secure location for mounting the unit. Ensure adequate space for ventilation and access.
  2. Mark the mounting points on the wall using the pre-drilled holes on the back of the enclosure as a template.
  3. Secure the enclosure to the wall using appropriate fasteners (screws, anchors) suitable for the wall material.

4.2 การเชื่อมต่อสายไฟ

ตรวจสอบให้แน่ใจว่าได้ตัดการเชื่อมต่อไฟฟ้าทั้งหมดแล้วก่อนที่จะทำการต่อสายไฟใดๆ

  1. อินพุตไฟฟ้ากระแสสลับ: Connect the 115VAC 60Hz power source to the designated AC input terminals on the main power supply board. Ensure proper grounding.
  2. การเชื่อมต่อแบตเตอรี่: Connect a 12V, 12AH sealed lead-acid battery to the battery terminals (Pb+ and Pb-). Observe correct polarity (red to positive, black to negative).
  3. เอาต์พุต DC: Connect your access control devices or other equipment requiring 12VDC power to the eight independent output terminals on the distribution board. Each output is fuse-protected.
  4. ยกเลิกการเชื่อมต่อสัญญาณเตือนไฟไหม้: If utilizing the fire alarm disconnect feature, connect the fire alarm control panel's normally closed (NC) contacts to the designated fire alarm disconnect terminals. Refer to the internal wiring diagram for specific connections.
  5. การต่อลงดิน: Ensure the enclosure is properly grounded using the green ground wire provided or a suitable grounding connection.

5. คู่มือการใช้งาน

เมื่อการเชื่อมต่อทั้งหมดเสร็จสมบูรณ์และได้รับการตรวจสอบอย่างปลอดภัยแล้ว:

  1. Apply 115VAC power to the unit.
  2. Observe the status indicator LEDs on the main power supply board and the distribution board. Refer to the internal diagram for LED indications (e.g., AC OK, Battery Charge, Output Status).
  3. Verify that all connected devices are receiving power and functioning correctly.
  4. Test the fire alarm disconnect feature if it has been implemented, ensuring it properly cuts power to the configured outputs.

6. การบำรุงรักษา

Regular maintenance helps ensure the longevity and reliable operation of your AL1012ULACMCB unit.

  • การทำความสะอาด: Periodically clean the exterior of the enclosure with a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure ventilation openings are free from dust and debris.
  • การตรวจสอบแบตเตอรี่:
    • Inspect battery terminals for corrosion. Clean if necessary.
    • ตรวจสอบปริมาณแบตเตอรี่tage periodically. A fully charged 12V sealed lead-acid battery should read approximately 12.6V to 12.8V.
    • Replace the battery every 3-5 years, or sooner if its capacity significantly degrades.
  • การตรวจสอบฟิวส์: Periodically check the fuses on the distribution board. If an output is not functioning, check its corresponding fuse. Replace blown fuses only with the same type and rating.
  • ความสมบูรณ์ของการเชื่อมต่อ: Annually check all wiring connections for tightness and signs of wear or damage.

7 การแก้ไขปัญหา

ปัญหาสาเหตุที่เป็นไปได้สารละลาย
No power to outputs.No AC input; Blown fuse on main board; Faulty power supply board.Check AC power source and connections. Inspect main board fuse. Contact technical support if board is faulty.
Specific output not working.Blown fuse for that output; Short circuit on output line; Device fault.Check and replace the specific output fuse. Disconnect device and check for short. Test device separately.
Battery not charging or holding charge.Loose battery connections; Defective battery; Faulty charging circuit.Verify battery connections. Test battery with a multimeter; replace if defective. Contact support if charging circuit is faulty.
Fire alarm disconnect not functioning.Incorrect wiring; Fire alarm panel issue; Output not configured for disconnect.Verify wiring to fire alarm panel. Check fire alarm panel output. Ensure outputs are correctly selected for disconnect.

8. ข้อมูลจำเพาะ

ข้อมูลจำเพาะค่า
หมายเลขรุ่นAL1012ULACMCB
อินพุต Voltage115VAC, 60Hz
ปริมาณการส่งออกtage12VDC
Total Supply Current10 Amp (ต่อเนื่อง)
จำนวนผลผลิต8 (independently controlled, fuse protected)
ประเภทเอาท์พุตNon-power limited, selectable Fail-Safe/Fail-Secure
ประเภทแบตเตอรี่กรดตะกั่วปิดผนึก
ความต้องการแบตเตอรี่2 12V batteries required (e.g., 12V, 12AH)
น้ำหนักสินค้า11.02 ปอนด์
ผู้ผลิตบริษัท อัลทรอนิกซ์ คอร์ปอเรชั่น
วันที่พร้อมใช้งานครั้งแรก31 กรกฎาคม 2010

9. การสนับสนุนและการรับประกัน

For technical support, service, or warranty information, please contact Altronix Corporation directly. Refer to the official Altronix webไซต์หรือบรรจุภัณฑ์ผลิตภัณฑ์สำหรับรายละเอียดการติดต่อล่าสุดและเงื่อนไขการรับประกัน

Note: This manual provides general guidance. Specific installation and operational details may vary. Always refer to the detailed wiring diagrams and instructions provided inside the product enclosure or on the manufacturer's official documentation.

เอกสารที่เกี่ยวข้อง - AL1012ULACMCB

พรีview Altronix ACM Series Access Power Controllers พร้อมคู่มือการติดตั้งพาวเวอร์ซัพพลาย
This installation guide provides detailed instructions for the Altronix ACM Series Access Power Controllers with Power Supplies, including models AL400ULACM, AL600ULACM, AL1012ULACM, and AL1024ULACM. It covers power supply options, input and output configurations, fire alarm interface, and maintenance.
พรีview Altronix AL1024NKA8 Series Dual Output Access Power Controllers คู่มือการติดตั้ง
This document provides comprehensive installation instructions for the Altronix AL1024NKA8 and AL1024NKA8D Dual Output Access Power Controllers. It covers product overview, specifications, wiring diagrams, battery calculations, maintenance, and LED diagnostics.
พรีview Altronix Trove1/Mercury Kits Installation Guide
Comprehensive installation guide for Altronix Trove1/Mercury Kits, detailing models T1MK14, T1MK14D, T1MK14S, and T1MK14SD, including product overviewแผนภูมิการกำหนดค่า ขั้นตอนการติดตั้ง และขนาดของกล่องหุ้ม
พรีview Altronix MaximalDV Series Access Power Controllers Installation Guide
Installation guide for Altronix MaximalDV Series Access Power Controllers, covering models Maximal11DV, Maximal33DV, Maximal55DV, Maximal75DV, and Maximal77DV. Details features, specifications, wiring, and maintenance for access control systems.
พรีview Altronix/Trove3 Mercury Kits Installation Guide
Comprehensive installation guide for Altronix Trove3 Mercury Kits, detailing models T3MK75F16, T3MK75F16D, T3MK77F16, and T3MK77F16D. Covers product overview, configuration chart, hardware, mechanical specifications, step-by-step installation instructions, and LINQ2 network module features.
พรีview คู่มือการติดตั้งตัวควบคุมการเข้าออก Altronix Maximal V Series พร้อมแหล่งจ่ายไฟคู่
This installation guide provides comprehensive instructions for setting up and configuring the Altronix Maximal V Series Dual Power Supply Access Power Controllers. Designed for robust access control systems, these units offer 16 fused, independently controlled outputs with dual power supply capabilities.