Sure-Lites LPX7

Sure-Lites LPX7 Universal Emergency Exit Light User Manual

Model: LPX7 | Brand: Sure-Lites

การแนะนำ

The Sure-Lites LPX7 Series LED Exit Light is a universal emergency exit sign designed for general purpose applications. This unit features a durable polycarbonate housing and is equipped with LED lamps, offering energy efficiency and reliability. It supports dual voltage input (120/277 VAC) and includes a nickel cadmium battery for emergency operation, providing a minimum run time of 90 minutes during power loss.

The LPX7 series is engineered for ease of installation and maintenance, making it a suitable replacement for previous models like the CCX Series. It ships with components to configure either red or green exit legends, providing flexibility for various installation requirements.

Sure-Lites LPX7 Universal Emergency Exit Light

Figure 1: Sure-Lites LPX7 Universal Emergency Exit Light with red legend illuminated.

ข้อมูลด้านความปลอดภัย

โปรดอ่านและทำความเข้าใจคำแนะนำทั้งหมดก่อนติดตั้งหรือใช้งานผลิตภัณฑ์นี้ การไม่ปฏิบัติตามคำแนะนำเหล่านี้อาจส่งผลให้เกิดไฟฟ้าช็อต ไฟไหม้ หรืออันตรายอื่น ๆ ที่อาจทำให้ทรัพย์สินเสียหายหรือได้รับบาดเจ็บ

เนื้อหาแพ็คเกจ

ตรวจสอบว่าส่วนประกอบทั้งหมดอยู่ครบถ้วนและไม่ได้รับความเสียหายก่อนเริ่มการติดตั้ง:

การติดตั้งและการตั้งค่า

The LPX7 exit sign is designed for universal mounting, allowing for ceiling, wall, or end mount installations. Follow these steps for proper setup:

1. การเลือกสถานที่

Choose a mounting location that is visible and meets local building codes for emergency exit signage. Ensure the mounting surface is structurally sound to support the unit's weight.

2. การตัดกระแสไฟฟ้า

Before starting any electrical work, turn off power to the circuit at the main breaker panel to prevent electric shock.

3. การเตรียมการติดตั้ง

Determine the desired mounting method (ceiling, wall, or end mount). The unit is designed for semi-flush mount installation. Refer to the dimensions diagram for precise measurements.

Dimensions of Sure-Lites LPX7 Emergency Exit Light

Figure 2: Dimensional drawing of the LPX7 exit light, showing overall width of 13 inches (330mm), overall height of 7 1/2 inches (190mm), and overall depth of 2 1/8 inches (54mm).

4. การเชื่อมต่อไฟฟ้า

Connect the unit to a 120 VAC or 277 VAC, 60 Hz power source. The LPX7 features dual voltage input. Ensure proper wiring according to the provided wiring diagram (typically found inside the unit or on a separate sheet). All connections must be secure and insulated.

5. การเชื่อมต่อแบตเตอรี่

Connect the internal Nickel Cadmium (NiCAD) battery. The battery is typically pre-installed but may require connecting a small plug to the circuit board. Ensure the connection is firm.

6. Legend Configuration

Insert the desired red or green legend panels into the unit. The LPX7 ships with both options, allowing for field configuration.

7. การประกอบขั้นสุดท้าย

Secure the unit to the mounting surface using the provided hardware. Ensure the housing is properly closed and secured.

8. Power Restoration & Testing

Restore power to the circuit. The exit sign should illuminate. Press the "TEST" button (usually a small push-button on the side or bottom of the unit) to verify emergency operation. The unit should switch to battery power and remain illuminated for at least 30 seconds. Release the button, and the unit should return to AC power.

การดำเนินการ

The Sure-Lites LPX7 Emergency Exit Light operates automatically. When connected to a continuous AC power source, the LED lamps will remain illuminated, indicating the exit path. The internal Nickel Cadmium battery continuously charges while AC power is present.

โหมดฉุกเฉิน

ในกรณีไฟฟ้าดับtage or interruption to the AC supply, the unit will automatically switch to emergency mode, drawing power from its internal battery. The LED lamps will remain illuminated for a minimum of 90 minutes, providing essential egress lighting.

ปุ่มทดสอบ

A test button is provided on the unit for routine maintenance checks. Pressing and holding this button simulates a power failure, allowing you to verify that the battery and lamps are functioning correctly in emergency mode. Release the button to return to normal AC operation.

Emergency exit light installed in a waiting area

รูปที่ 3: อดีตample installation of an emergency exit light in a commercial waiting area, demonstrating its function in a public space.

Emergency exit light installed in an auditorium

รูปที่ 4: อดีตample installation of an emergency exit light in an auditorium, highlighting its visibility in a large gathering space.

การซ่อมบำรุง

Regular maintenance ensures the continued reliable operation of your emergency exit light. Always disconnect power before performing any maintenance.

การทดสอบรายเดือน

Perform a monthly 30-second test by pressing the test button. The unit should operate on battery power for the duration of the test. If the lamps do not illuminate or dim significantly, the battery may need replacement or further charging.

Annual Testing

Conduct an annual 90-minute discharge test. Disconnect AC power to the unit and allow it to operate on battery power for 90 minutes. The lamps should remain illuminated for the entire duration. If the unit fails to operate for 90 minutes, the battery requires replacement.

การทำความสะอาด

Clean the exterior of the unit periodically with a soft, damp cloth. Do not use abrasive cleaners or solvents, as these can damage the polycarbonate housing.

การเปลี่ยนแบตเตอรี่

The Nickel Cadmium battery has a typical lifespan of 5-7 years. If the unit fails to meet the required emergency run time during testing, replace the battery with an approved Sure-Lites replacement battery. Ensure proper polarity when connecting the new battery.

การแก้ไขปัญหา

If your Sure-Lites LPX7 Emergency Exit Light is not functioning as expected, refer to the following common issues and solutions:

ปัญหาสาเหตุที่เป็นไปได้สารละลาย
Unit does not illuminate when AC power is on.No AC power to the unit; Loose wiring connection; Faulty LED lamps.Check circuit breaker and power supply. Verify all wiring connections are secure. Contact qualified service personnel if lamps มีข้อบกพร่อง
Unit does not illuminate in emergency mode (during test or power outagจ).Battery not connected; Battery not charged; Battery has reached end of life; Faulty circuit board.Ensure battery is properly connected. Allow 24 hours for initial battery charge. Replace battery if it fails annual test. Contact qualified service personnel.
Lamps are dim in emergency mode.Battery not fully charged; Battery nearing end of life.Allow unit to charge for 24 hours. If problem persists, replace battery.

If the problem persists after attempting these solutions, contact Sure-Lites customer support or a qualified electrician.

ข้อมูลจำเพาะ

คุณสมบัติรายละเอียด
หมายเลขรุ่นแอลพีเอ็กซ์7
อินพุต Voltage120/277 โวลต์ 60 เฮิร์ต
แหล่งกำเนิดแสงLED (2 Lamps)
อุณหภูมิสี5000K
Legend ColorConfigurable Red or Green
Legend Height6 นิ้ว
ประเภทการติดตั้งUniversal (Ceiling, Wall, End Mount)
วัสดุที่ใช้ทำตัวเรือนโพลีคาร์บอเนต
สีตัวเรือนสีขาว
ประเภทแบตเตอรี่Nickel Cadmium (NiCAD)
เวลาเรียกใช้ฉุกเฉินขั้นต่ำ 90 นาที
ความสูงรวม7.5 นิ้ว (190 มม.)
ความกว้างรวม13 นิ้ว (330 มม.)
ความลึกโดยรวม2.125 นิ้ว (54 มม.)
น้ำหนักสินค้า2.88 ปอนด์

การรับประกันและการสนับสนุน

ข้อมูลการรับประกัน

The Sure-Lites LPX7 Emergency Exit Light comes with a รับประกัน 5 ปี from the date of purchase. This warranty covers defects in materials and workmanship under normal use and service. The warranty does not cover damage resulting from improper installation, misuse, abuse, or acts of nature.

การสนับสนุนลูกค้า

For technical assistance, warranty claims, or replacement parts, please contact Sure-Lites customer support. Refer to the Sure-Lites official webไซต์หรือบรรจุภัณฑ์ผลิตภัณฑ์เพื่อให้มีข้อมูลติดต่อล่าสุด

บันทึก: Always provide your product model number (LPX7) and date of purchase when contacting support to expedite assistance.

เอกสารที่เกี่ยวข้อง - แอลพีเอ็กซ์7

พรีview ไดร์เวอร์ไฟ LED ฉุกเฉิน Sure-Lites EBPLEDL6SF - ข้อมูลจำเพาะและรายละเอียดผลิตภัณฑ์
ข้อมูลจำเพาะโดยละเอียด คุณสมบัติ และข้อมูลการติดตั้งสำหรับไดร์เวอร์ไฟ LED ฉุกเฉิน Sure-Lites EBPLEDL6SF จาก Cooper Lighting Solutions รวมถึงข้อมูลผลิตภัณฑ์เพิ่มเติมviewข้อมูลทางเทคนิค ใบรับรอง และแบบร่างแสดงขนาด
พรีview คู่มือการติดตั้งบัลลาสต์ฉุกเฉิน Sure-Lites EBP1400NCX/NCF
คู่มือการติดตั้ง การใช้งาน และการบำรุงรักษาที่ครอบคลุมสำหรับบัลลาสต์ฉุกเฉิน Sure-Lites EBP1400NCX และ EBP1400NCF พร้อมรายละเอียดเกี่ยวกับข้อควรระวังด้านความปลอดภัย แผนผังสายไฟ และamp ความเข้ากันได้
พรีview Sure-Lites FirstLink Connected Emergency Lighting System | Cooper Lighting Solutions
Explore the Sure-Lites FirstLink connected emergency lighting system from Cooper Lighting Solutions. This brochure details system features, hardware, app control, and service plans designed for building safety and code compliance.
พรีview Sure-Lites ELX Series LED Exit Sign - Technical Specifications
Detailed technical specifications for the Sure-Lites ELX Series self-powered LED exit signs, including features, construction, code compliance, energy data, and mounting options.
พรีview Sure-Lites APEL Series Emergency Lighting Fixture
Explore the Sure-Lites APEL Series emergency light, featuring UL 924 listing, 90-minute runtime, adjustable LED heads, and a durable nickel cadmium battery. Ideal for reliable emergency egress with remote capacity options.
พรีview Sure-Lites All-Pro APX RG Series LED Exit Sign - Technical Specifications
Detailed specifications for the Sure-Lites All-Pro APX RG Series LED Exit Sign, featuring thermoplastic housing, selectable red or green faces, AC-only or battery backup options, and compliance with UL924 and California Title 20.