GEYA GRL8

GEYA GRL8 Liquid Level Control Relay Instruction Manual

Models: GRL8-01, GRL8-02

1. บทนำ

The GEYA GRL8 series liquid level control relays are designed for precise monitoring and control of liquid levels in various applications. These devices are ideal for managing water levels in wells, basins, reservoirs, and tanks, ensuring efficient operation of pumps for filling or emptying. The GRL8 series offers robust performance with flexible configuration options to suit diverse industrial and domestic needs.

2. คุณสมบัติหลัก

  • Model GRL8-01: Provides 2-level control mode.
  • Model GRL8-02: Offers 2 or 1 level control mode, providing greater flexibility.
  • การเลือกฟังก์ชั่น: User-selectable PUMP UP (filling) or PUMP DOWN (emptying) functions.
  • ปรับเวลาล่าช้า: Output time delay adjustable from 0.1 to 10 seconds.
  • ความไวที่ปรับได้: Sensitivity (input resistance) can be adjusted via a potentiometer from 5 kΩ to 100 kΩ.
  • ปริมาณอุปทานกว้างtage: Galvanically separated supply voltage AC/DC 24-240V.
  • ติดต่อเอาท์พุท: 1 SPDT (Single Pole Double Throw) output with a rating of 10A/AC1.
  • การแสดงสถานะ: Relay status is clearly indicated by an LED.
  • การติดตั้ง: Compact 1-MODULE design for DIN rail mounting.

3. ข้อมูลจำเพาะทางเทคนิค

Refer to the table below for detailed technical parameters of the GRL8 series relays:

Technical Parameters Table for GEYA GRL8-01 and GRL8-02 Liquid Level Control Relays

Image: Technical Parameters for GRL8-01 and GRL8-02 models.

พารามิเตอร์ GRL8-01 (2 level control mode) GRL8-02 (2 or 1 level control mode)
การทำงาน2 level control mode2 or 1 level control mode
ขั้วอุปทานA1-A2A1-A2
เล่มที่tagช่วงอีไฟฟ้ากระแสสลับ/กระแสตรง 24-240V (50-60Hz)ไฟฟ้ากระแสสลับ/กระแสตรง 24-240V (50-60Hz)
ป้อนข้อมูลสูงสุด 2VAสูงสุด 2VA
ปริมาณอุปทานtagอี ความอดทน-15%; +10%-15%; +10%
Sensitivity (input resistance)adjustable in range 5 kΩ - 100 kΩadjustable in range 5 kΩ - 100 kΩ
เล่มที่tage in electrodesmax. AC 5Vmax. AC 5V
Current in probeAC < 0.1 mAAC < 0.1 mA
การตอบสนองเวลาสูงสุด 400 มิลลิวินาทีสูงสุด 400 มิลลิวินาที
Max. capacity length800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)
Max. capacity of probe cable400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)
Time delay (t)adjustable, 0.1 - 10 sadjustable, 0.1 - 10 s
Accuracy in setting (mechanical)± 10%± 10%
ค่าสัมประสิทธิ์อุณหภูมิ0.05%/°C, at +20°C (0.05°F, at =68°F)0.05%/°C, at +20°C (0.05°F, at =68°F)
ตัวบ่งชี้เอาต์พุตไฟ LED สีแดงไฟ LED สีแดง
อายุการใช้งานของเครื่องจักร1×10⁷1×10⁷
Electrical life (AC1)1×10⁵1×10⁵
รีเซ็ตเวลาmax. 200msmax. 200ms
อุณหภูมิในการทำงาน-20°C ถึง +55°C (-4°F ถึง 131°F)-20°C ถึง +55°C (-4°F ถึง 131°F)
อุณหภูมิในการเก็บรักษา-35°C ถึง +75°C (-22°F ถึง 158°F)-35°C ถึง +75°C (-22°F ถึง 158°F)
การติดตั้ง/ราง DINราง DIN EN/IEC 60715ราง DIN EN/IEC 60715
ระดับการป้องกันIP40 สำหรับแผงด้านหน้า/เทอร์มินอล IP20IP40 สำหรับแผงด้านหน้า/เทอร์มินอล IP20
ตำแหน่งการทำงานใดๆใดๆ
โอเวอร์โวลtage หมวดหมู่สาม.สาม.
ระดับมลพิษ22
Max. cable size(mm²)solid wire max. 1×2.5 or 2×1.5/ with sleeve max. 1×2.5 (AWG 12)solid wire max. 1×2.5 or 2×1.5/ with sleeve max. 1×2.5 (AWG 12)
ขนาด90×18×64มม.90×18×64มม.

หมายเหตุ: ข้อมูลจำเพาะอาจมีการเปลี่ยนแปลงได้โดยไม่ต้องแจ้งให้ทราบล่วงหน้า

ขนาด

GEYA GRL8 Relay Dimensions Diagram

Image: Physical dimensions of the GRL8 series relay in millimeters.

4. สินค้าหมดview

The GRL8 series relays are designed for easy integration into control panels. Below are diagrams illustrating the main components and their functions.

GRL8-01 Function Diagram

GRL8-01 Function Diagram with labeled components

Image: Labeled components for GRL8-01, including Supply Voltage Terminals (A1, A2), Max/Min Level Sensor connections, Supply Indication (GREEN), Relay Status Indication (RED), Sensitivity Setting, Model No., Level Monitoring Circuit Terminal (C, 11, 12, 14), and Output Contact.

GRL8-02 Function Diagram

GRL8-02 Function Diagram with labeled components

Image: Labeled components for GRL8-02, similar to GRL8-01 but also showing the PUMP UP or DOWN function selector.

5. การติดตั้งและการเดินสายไฟ

The GRL8 relays are designed for DIN rail mounting. Ensure all power is disconnected before installation and wiring. Follow local electrical codes and safety regulations.

แผนผังการเดินสายไฟ

Comprehensive Wiring Diagram, Panel Diagram, and Functions Diagram for GRL8 relays

Image: Detailed wiring diagram showing connections for power supply (Un), level sensors (Max, Min, C), and output contacts (11, 12, 14). Also includes panel layout and function diagrams.

การเชื่อมต่อเซ็นเซอร์:

  • เชื่อมต่อ Common Probe (C) to the lowest point of liquid detection.
  • เชื่อมต่อ Min Level Probe (Min) for the minimum liquid level.
  • เชื่อมต่อ Max Level Probe (Max) for the maximum liquid level.
  • Ensure probes are securely installed and insulated from each other, except through the liquid.

การเชื่อมต่อขาออก:

  • The relay has a 1SPDT output. Terminals 11, 12, and 14 are available.
  • Terminal 11 is the Common contact.
  • Terminal 12 is Normally Closed (NC).
  • Terminal 14 is Normally Open (NO).
  • Connect your pump or control device to the appropriate contacts (e.g., 11 and 14 for pump activation when liquid level changes).

6. การดำเนินการ

The GRL8 series relays can be configured for two primary operation modes: PUMP UP (filling) and PUMP DOWN (emptying).

Operation Modes Explained

  • PUMP UP (Filling Mode): The pump activates when the liquid level drops below the 'Min' probe and deactivates when it reaches the 'Max' probe. This mode is used to fill a tank.
  • PUMP DOWN (Emptying Mode): The pump activates when the liquid level reaches the 'Max' probe and deactivates when it drops below the 'Min' probe. This mode is used to empty a tank.

การปรับเปลี่ยน:

  • ความไว: Use the 'Sensitivity' potentiometer to adjust the input resistance (5-100K) based on the conductivity of the liquid and the length of the sensor cables.
  • Time Delay (Tt): Use the 'Tt' potentiometer to set a time delay (0.1-10s) for the output. This prevents rapid switching due to minor liquid fluctuations.

การสาธิตด้วยภาพ

Video: Demonstration of the GRL8 relay controlling liquid levels for both pump down and pump up scenarios.

7. เคล็ดลับผู้ใช้

  • Sensor Cable Extension: Sensors can typically be extended. Users have reported successful extensions up to 10 meters using standard twisted pair cables. For longer distances or specific environments, consult the technical specifications for maximum capacity length and probe cable capacity.
  • Direct Pump Connection: For pumps up to 2kW (10A at 220V), direct connection to the relay's output contacts (11/12 or 11/14) is generally possible without an additional contactor. Always verify the pump's power requirements against the relay's maximum contact load.
  • การติดตั้งเซ็นเซอร์: Sensors can be simply suspended at the desired maximum, minimum, and common liquid levels within the tank or container. Ensure they are stable and do not move freely.
  • เสียงการทำงานปกติ: It is normal to hear a faint clicking sound from the relay when it switches on or off, indicating proper operation of the internal mechanism.
  • Filling vs. Draining: When setting up, ensure you correctly select the 'PUMP UP' (filling) or 'PUMP DOWN' (draining) mode based on your application to prevent unintended pump behavior.

8 การแก้ไขปัญหา

  • รีเลย์ไม่ทำงาน:
    • Check power supply to terminals A1 and A2.
    • Verify sensor connections to Max, Min, and C terminals.
    • Ensure liquid level is within the detection range of the probes.
    • Adjust 'Sensitivity' potentiometer, especially for liquids with low conductivity or long sensor cables.
    • Check the 'Time Delay (Tt)' setting; a long delay might cause perceived non-activation.
  • Pump Not Responding to Relay:
    • Confirm correct wiring of the pump to the output contacts (11, 12, 14).
    • วัดปริมาตรtage at the output contacts (e.g., between 11 and 14 when activated) to ensure the relay is providing power. If voltage is low (e.g., 0-0.3V), there might be an internal fault or incorrect wiring.
    • Ensure the pump's power rating does not exceed the relay's 10A/AC1 contact rating. For higher power pumps, an external contactor is required.
  • การทำงานที่ไม่แน่นอน:
    • Check for loose sensor connections or damaged sensor cables.
    • Ensure probes are clean and free from deposits that might affect conductivity.
    • Adjust sensitivity to match liquid properties.
    • Increase time delay if rapid liquid fluctuations are causing frequent switching.

9. การบำรุงรักษา

  • การทำความสะอาดเซ็นเซอร์: Periodically inspect and clean the liquid level sensors, especially in environments prone to mineral deposits, sludge, or other contaminants (e.g., septic tanks). Buildup on the probes can interfere with accurate level detection.
  • การตรวจสอบการเชื่อมต่อ: Regularly check all electrical connections for tightness and signs of corrosion or damage.
  • สภาพแวดล้อม : Ensure the relay is operating within its specified temperature and protection degree (IP40 for front panel/IP20 terminals) to prolong its lifespan.

10. การรับประกันและการสนับสนุน

GEYA products are manufactured to high-quality standards. For any technical assistance, warranty claims, or support inquiries, please contact your authorized GEYA distributor or the GEYA Official Store. Please have your product model number and purchase details ready when contacting support.

© 2024 GEYA. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.