ESBE 43102800
ESBE MBA132 DN25 3-Way Motorized Ball Valve User Manual
Model: MBA132
การแนะนำ
This manual provides essential information for the installation, operation, and maintenance of the ESBE MBA132 DN25 3-Way Motorized Ball Valve. The MBA130 series valves are designed for efficient switching in heating and cooling systems, ensuring reliable performance and bubble-tight sealing according to EN12266-1. Please read this manual thoroughly before installation and operation to ensure safe and correct usage.
สินค้าเกินview

The image displays a typical ESBE motorized ball valve, similar to the MBA132 model. It consists of a metallic 3-way ball valve body with threaded connections (visible as G 1" in the product title, though the image shows DN 20 / 3/4"). Mounted on top is a black electrical actuator, labeled 'ESBE MBA100', which controls the valve's position. The actuator is powered by 230V AC and features a 0.85m long electrical cable for connection. The unit is designed for a 90° rotation angle, facilitating on/off or diverting functions in fluid systems. The actuator also includes an anti-condensation resistor for enhanced durability.
- ประเภทวาล์ว: บอลวาล์ว 3 ทาง
- ประเภทตัวกระตุ้น: 2-point control, On/Off function
- แหล่งจ่ายไฟ: 230 V AC, 50 เฮิร์ตซ์
- มุมการหมุน: 90°
- การปิดผนึก: Bubble-tight according to EN12266-1
- คุณสมบัติ: Auxiliary switch, anti-condensation resistor
การติดตั้งและการตั้งค่า
1. การเปิดออกและการตรวจสอบ
Carefully remove the valve and actuator from its packaging. Inspect all components for any signs of damage during transit. Ensure all parts, including the valve body, actuator, and any included screw kit, are present.
2. Mounting the Valve
The MBA132 valve is designed for easy integration into piping systems. It features external G 1" threads for connection. Ensure the system is depressurized and drained before installation. Apply appropriate thread sealant to ensure a leak-free connection. The valve can be installed in any orientation, but ensure sufficient space for the actuator and future maintenance.
3. Attaching the Actuator
The actuator is designed for quick and easy attachment to the ball valve using a pin mechanism. Align the actuator with the valve stem and secure it firmly. Ensure the actuator is properly seated and locked into place to allow for correct valve operation.
4. การเชื่อมต่อไฟฟ้า
The actuator requires a 230 V AC, 50 Hz power supply. Connect the 0.85m cable to the appropriate electrical terminals. The actuator features a 2-point control for on/off functionality and an additional auxiliary switch. Consult a qualified electrician for wiring if you are unsure. Ensure all electrical connections comply with local regulations and safety standards.
คำแนะนำการใช้งาน
The ESBE MBA132 operates with a simple on/off function, controlled by the 2-point actuator. When power is applied, the actuator rotates the ball valve 90° to either an open or closed position, or to divert flow in a 3-way configuration. The auxiliary switch can be used to provide feedback on the valve's position or to control other components in the system.
- เปิดเครื่อง: Applying power to the actuator will initiate a rotation to its designated position.
- หมดแรง: Removing power will typically cause the actuator to remain in its last position, or return to a default position if designed for spring return (check specific model details).
- การแทนที่ด้วยตนเอง: Some actuators may have a manual override lever or knob. Refer to the actuator's specific instructions if manual operation is required.
การซ่อมบำรุง
The ESBE MBA132 valve and actuator are designed for long-term, maintenance-free operation under normal conditions. However, periodic checks are recommended:
- การตรวจสอบภาพ: ตรวจสอบวาล์วและตัวขับเคลื่อนอย่างสม่ำเสมอเพื่อหาสัญญาณของการรั่วซึม การกัดกร่อน หรือความเสียหายทางกายภาพ
- ความสมบูรณ์ของการเชื่อมต่อ: Ensure all pipe connections are secure and free from leaks. Check electrical connections for tightness and integrity.
- ฟังก์ชั่นตัวกระตุ้น: Periodically observe the actuator's operation to ensure smooth and complete rotation.
- Anti-Condensation Resistor: The integrated anti-condensation resistor helps protect the internal electronics. No user maintenance is required for this feature.
Before performing any maintenance, ensure the system is depressurized, drained, and the power supply to the actuator is disconnected.
การแก้ไขปัญหา
| ปัญหา | สาเหตุที่เป็นไปได้ | สารละลาย |
|---|---|---|
| ตัวกระตุ้นไม่เคลื่อนที่ | No power supply; Incorrect wiring; Actuator fault | Check power supply and circuit breaker. Verify wiring connections. If problem persists, contact support. |
| วาล์วไม่เปิด/ปิดเต็มที่ | Obstruction in valve; Actuator not properly mounted; Actuator fault | Inspect valve for debris. Re-check actuator mounting. Contact support if mechanical issue. |
| Leakage from valve connections | Improperly sealed threads; Damaged threads/fittings | Ensure proper thread sealant was used and connections are tight. Replace damaged components if necessary. |
ข้อมูลจำเพาะ
| คุณลักษณะ | ค่า |
|---|---|
| หมายเลขรุ่น | MBA132 (Reference: 43102800) |
| ชนิดของวาล์ว | บอลวาล์ว 3 ทาง |
| ขนาดการเชื่อมต่อ | DN25 (G 1" external thread) |
| Actuator Power Supply | 230 V AC, 50 เฮิร์ตซ์ |
| การใช้พลังงาน | 0-8.5เวอร์จิเนีย |
| แรงบิด | 10 นิวตันเมตร |
| Rotation Time (90°) | 40 วินาที |
| ระดับการป้องกัน | IP44 (as per image, typical for series) |
| ความยาวสายเคเบิล | 0.85 เมตร |
| ขนาด (กว้าง x ยาว x สูง) | Approximately 1 x 1 x 1 cm (Product dimensions: 1 x 1 x 1 cm) |
| น้ำหนัก | 1.51 กิโลกรัม |
| สี | Black (Actuator) |
| ต้นทาง | Made in EU (as per image, typical for series) |
การรับประกันและการสนับสนุน
ข้อมูลการรับประกัน
This product typically comes with a return policy allowing for refunds or replacements within 30 days of purchase. For specific warranty terms and conditions, please refer to your purchase documentation or contact your retailer.
การสนับสนุนลูกค้า
For technical assistance, troubleshooting beyond this manual, or warranty claims, please contact the manufacturer, ESBE, or your authorized distributor. Provide your product model number (MBA132) and any relevant purchase details when seeking support.
Ask a question about this manual
Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.